120-Ton R134a Shell-and-Tube Evaporator for Turbocor Chiller
Time :Aug 28, 2026

A shell-and-tube evaporator suitable for a 120-ton centrifugal chiller must provide approximately 422 kW of refrigeration capacity while maintaining stable R134a evaporation, low chilled-water pressure drop and reliable compressor suction conditions. The proposed exchanger uses R134a on the shell side and chilled water inside the tubes, with a three-pass water circuit and approximately 120–160 tubes.


The chilled water enters at 12°C and leaves at 7°C, producing a design temperature difference of 5 K. Based on a cooling capacity of 422 kW, the calculated chilled-water mass flow is approximately 20.2 kg/s. This is equivalent to roughly 72–74 m³/h, depending on water density and whether glycol is present. Pump heat, external heat gain and the required thermal design margin should be included when determining the final rated capacity.


Using ¾-inch tubes in a three-pass arrangement is practical for this water flow. With approximately 120 tubes, each pass would contain about 40 parallel tubes. With 150 tubes, each pass would contain approximately 50 tubes, while 160 tubes would provide about 53 tubes per pass. The selected number must also allow equal circuiting between all three passes.


For a typical tube internal diameter near 16–17 mm, the resulting water velocity is expected to be approximately 1.8–2.5 m/s across the proposed tube-count range. This is generally suitable for good heat transfer and helps limit internal fouling. However, the exact velocity and pressure drop must be recalculated after confirming the tube material and wall thickness.


TEMA does not prescribe one universal wall thickness for every ¾-inch heat-exchanger tube. The required thickness depends on tube material, design pressure, design temperature, corrosion allowance, manufacturing tolerance, tube-support spacing and the method used to join the tubes to the tubesheets. The final tube thickness should comply with the applicable pressure-vessel code and the agreed TEMA construction class.


The recommended tube length depends on whether plain or enhanced tubes are used. With conventional smooth tubes, the evaporator may require a relatively long bundle to provide sufficient surface area. For a 120-ton R134a evaporator with 120–160 tubes, a preliminary smooth-tube length could fall in the range of approximately 5–7 metres, depending on evaporating temperature and the overall heat-transfer coefficient.


Refrigeration evaporators commonly use enhanced tubes with internal rifling and external boiling surfaces. These tubes increase water-side turbulence and improve refrigerant boiling on the shell side. With suitable enhanced tubes, the required bundle length may be reduced to approximately 3.5–5 metres. Final tube length should be selected through a complete thermal rating rather than by applying a fixed length-to-capacity ratio.


The evaporating temperature is one of the most important missing design conditions. For chilled water leaving at 7°C, an R134a evaporating temperature of approximately 2–4°C may be considered as an initial basis, depending on the required approach temperature. A lower evaporation temperature increases the temperature difference across the exchanger but reduces compressor efficiency and may increase the risk of water freezing during abnormal operation.


The preliminary logarithmic mean temperature difference will normally be around 6–8 K for this chilled-water range. The exact value depends on the saturation temperature and any refrigerant superheat. Once the evaporating temperature is confirmed, the required heat-transfer area can be calculated from the thermal duty, corrected temperature difference, overall heat-transfer coefficient and specified fouling factors.


R134a should normally flow on the shell side, where it evaporates around the outside of the tube bundle. The water remains inside the tubes, allowing mechanical cleaning and providing reliable containment of the pressurized water circuit. This arrangement is suitable for flooded, falling-film or direct-expansion evaporator designs.


A flooded evaporator can provide effective use of the tube surface and stable refrigerant temperatures, but it requires a controlled refrigerant level and sufficient vapor-disengagement space above the bundle. A falling-film design can reduce the refrigerant charge but requires accurate liquid distribution. A direct-expansion design uses less refrigerant but requires careful circuiting to ensure uniform distribution and complete evaporation.

120-Ton R134a Shell-and-Tube Evaporator for Turbocor Chiller

The stated centrifugal-compressor suction flow of 600–800 CFM is equivalent to approximately 1,020–1,360 m³/h. This flow should be verified at the actual suction pressure and temperature because refrigerant volumetric flow changes substantially with density. The mass flow required for 422 kW will depend on the R134a enthalpy difference across the evaporator and the selected compressor operating point.


The suction-flow figure is especially important for sizing the refrigerant outlet nozzle, shell vapor space and internal separation devices. Excessive vapor velocity can carry liquid droplets into the compressor. Although an oil-free centrifugal compressor eliminates conventional oil-return problems, it remains sensitive to liquid refrigerant entering the suction line.


A 24-inch shell diameter may accommodate the proposed tube bundle, but its suitability cannot be confirmed from tube count alone. The shell must provide enough space for the 120–160 tubes, tube pitch, pass partitions, baffles or supports, refrigerant distribution and vapor disengagement. The available area above the bundle must also keep suction velocity below the allowable value.


If the 600–800 CFM suction flow produces excessive velocity inside a 24-inch shell, a larger shell diameter, an external suction separator or an enlarged vapor dome may be required. Maintaining the approximate 24-inch diameter should not take priority over reliable liquid separation and stable compressor operation.


A square tube pitch provides better access for mechanical cleaning, while a rotated-square or diamond pitch can fit more tubes into a given shell diameter and improve shell-side refrigerant distribution. Because chilled water flows inside the tubes, mechanical cleaning is performed from the channel ends rather than between the tubes. This allows a diamond arrangement to be considered if it improves bundle compactness and refrigerant-side performance.


The tube material should be chosen according to chilled-water quality. Enhanced copper tubes are commonly used because of their high thermal conductivity and established boiling performance with R134a. Copper-nickel, stainless steel or titanium may be considered for aggressive water, but these materials have different thermal characteristics and may require more surface area.


A three-pass water arrangement requires a removable channel cover with correctly positioned pass-partition plates. The partitions must seal properly against the cover gasket to prevent water bypass between passes. Water nozzles should be sized to control velocity and should be positioned to simplify piping and complete drainage.


The evaporator should include refrigerant inlet distribution, a sufficiently large suction connection, refrigerant-level connections where applicable, pressure and temperature instruments, safety-relief provisions, water drains and vents. A low-temperature cutout, flow switch and compressor interlock are necessary to protect the tubes against freezing when water flow is lost.


A suitable preliminary configuration is therefore a 24-inch or slightly larger shell with approximately 144–156 enhanced ¾-inch tubes, three chilled-water passes and an initial tube length of approximately 4–5 metres. This configuration should not be treated as a final selection until the R134a evaporation temperature, refrigerant mass flow, suction pressure, allowable water-side pressure drop, water fouling factor and required TEMA class are confirmed.