Seawater-Cooled Shell and Tube Heat Exchanger for Offshore Platform
Time :Jul 29, 2026

A shell and tube heat exchanger installed on a permanently moored offshore platform must be designed differently from a conventional marine cooler serving a sailing vessel. Because the platform has zero forward speed, there is no ram effect to assist seawater circulation. The complete cooling duty must therefore be supported by seawater pumps under every operating condition.

For this project, each cooler has a nominal duty of 5 MW. Freshwater forms the hot-side circuit, while seawater at 32°C removes heat from the system. The freshwater must leave the heat exchanger at 36°C, and the seawater outlet temperature must remain below 40°C.

The overall objective is not simply to manufacture a cooler that meets the thermal duty. The proposed design must reduce electrical consumption, limit chemical treatment and provide a lower lifetime cost for the offshore installation.

Seawater-Cooled Shell and Tube Heat Exchanger for Offshore Platform

Project Operating Conditions

Two hot-side operating cases are being considered.

ParameterCase 1Case 2
Heat duty5 MW5 MW
Hot-side mediumFreshwaterFreshwater
Cold-side mediumSeawaterSeawater
Freshwater flow600 m³/h1,200 m³/h
Freshwater inlet43.3°C39.6°C
Freshwater outlet36°C36°C
Seawater inlet32°C32°C
Maximum seawater outletBelow 40°CBelow 40°C
Freshwater operating pressure6 barg6 barg
Seawater operating pressure5 barg5 barg
Freshwater density990 kg/m³990 kg/m³
Seawater density1,025 kg/m³1,025 kg/m³
Freshwater specific heat4.16 kJ/kg·K4.16 kJ/kg·K
Seawater specific heat4.0 kJ/kg·K4.0 kJ/kg·K

The Case 1 data gives approximately 5 MW when the freshwater is cooled from 43.3°C to 36°C. Case 2 also represents approximately 5 MW, allowing for rounding in the stated temperatures and flow rate.


Preliminary Seawater Flow Calculation

For a 5 MW duty, the theoretical seawater flow required at different temperature rises is:

Seawater ConditionApproximate Flow
32°C to 40°C549 m³/h
32°C to 39°C627 m³/h
32°C to 38°C732 m³/h
32°C to 37°C878 m³/h
32°C to 36.5°C976 m³/h

The theoretical minimum is approximately 549 m³/h if the seawater reaches 40°C. However, this condition should not be used directly as the design point.

In Case 1, a 40°C seawater outlet would leave only a 3.3°C temperature difference between the incoming freshwater and outgoing seawater. This is technically possible but results in a tight thermal approach and a relatively large heat transfer surface.

Case 2 is more restrictive. The freshwater enters at only 39.6°C, so seawater cannot leave at 40°C. Even a 39°C seawater outlet would give a hot-end approach of only 0.6°C, which would require an impractically large heat exchanger.

A more realistic preliminary selection would therefore be:

  • Case 1: approximately 650–750 m³/h of seawater, with an outlet near 38–39°C.
  • Case 2: approximately 850–1,000 m³/h, with an outlet near 36.5–37.5°C.

The final flow should be selected through lifecycle optimization rather than by using the lowest possible pump flow. Reducing flow decreases pump power, but it also reduces the temperature driving force and increases the required heat transfer area. Excessively high flow reduces the exchanger size but increases pumping energy and may accelerate tube erosion.


Recommended Fluid Arrangement

For this offshore application, seawater should normally flow through the tubes, while freshwater flows through the shell.

Keeping seawater inside the tubes provides several practical advantages. The tubes can be mechanically cleaned from the channel ends, marine deposits can be inspected more easily, and the seawater inventory remains confined to a corrosion-resistant pressure boundary. Removable channel covers should be included so that the tubes can be brushed, hydro-jetted or inspected without removing the complete exchanger.

The freshwater side can use a carbon steel or stainless steel shell, depending on water chemistry and project requirements. Internal flow distribution must be carefully designed because both cases involve high freshwater flow rates.


Titanium or Copper-Nickel Tubes?

Material selection has a direct influence on capital cost, maintenance requirements and lifetime environmental impact.

Titanium Grade 2 tubes are the preferred option when long service life and low chemical dependence are the main priorities. Titanium provides excellent resistance to warm seawater, chlorides and general marine corrosion. It can also tolerate relatively high seawater velocity without the erosion-corrosion risks associated with some copper alloys.

A titanium design may use solid titanium tube sheets or titanium-clad carbon steel tube sheets. Although the initial investment is higher, titanium can reduce tube replacement, corrosion failures, unplanned shutdowns and chemical treatment over the platform lifetime.

Cu-Ni 90/10 tubes offer a lower initial cost and have a long history in marine cooling systems. They can be suitable when seawater quality, velocity and biological activity are properly controlled. However, they require more careful velocity management and may be less attractive when the site prioritizes minimal chemical dosing and maximum service life.

For this particular project, titanium should be evaluated as the base lifecycle option, with Cu-Ni 90/10 retained as the lower-capital-cost alternative.


Heat Exchanger Configuration

A straight-tube shell and tube cooler with removable seawater channel covers is a practical starting point. A fixed tube-sheet configuration can offer lower cost, fewer sealing points and easier fabrication if thermal stress analysis confirms that differential expansion is acceptable.

A removable bundle or floating-head arrangement may be considered when shell-side mechanical cleaning is required or when thermal expansion cannot be accommodated by a fixed tube-sheet construction. However, the additional gaskets, components and maintenance requirements should be evaluated against the lifetime-cost objective.

One-pass and two-pass seawater arrangements should both be studied. A two-pass arrangement may improve tube velocity and heat transfer, but it also increases seawater pressure drop. The final number of passes should be selected together with the seawater pump operating point.


Reducing Offshore Pumping Power

Because the platform has no forward motion, the seawater pumps will be continuous electrical consumers. Their power demand should therefore be included in the heat exchanger selection rather than treated as a separate system issue.

The cooler should be designed with generous nozzle sizes, low-loss water boxes and controlled tube-side velocity. Excessive tube length, unnecessary passes and abrupt internal flow changes should be avoided.

Variable-frequency-drive seawater pumps can regulate flow according to freshwater inlet temperature and actual cooling load. At reduced process load, the system can lower seawater flow while maintaining a minimum tube velocity that prevents sedimentation and poor heat transfer.

A duty-and-standby or N+1 pump arrangement provides offshore reliability without requiring all pumps to operate continuously.


Reducing Chemical Consumption

Warm seawater at 32°C creates a significant biofouling risk. A sustainable system should not depend entirely on continuous high-rate chlorination.

The exchanger can instead incorporate several complementary measures: suitable tube velocity, removable channel covers, automatic backwashing, mechanical tube cleaning or an online sponge-ball cleaning system. Side-stream filtration may also reduce suspended solids entering the tubes.

Where biological control remains necessary, intermittent electrochlorination or controlled low-dose treatment can be used rather than continuous excessive chemical injection. The exact strategy should be based on seawater analysis and local environmental discharge restrictions.

Titanium tubes are particularly useful in this approach because the material does not depend on a protective corrosion film in the same way as copper alloys. This gives greater flexibility in managing seawater chemistry.


Offshore Mechanical Design

The heat exchanger should be designed for continuous marine exposure and platform vibration. External carbon steel surfaces require a suitable offshore coating system, while fasteners, instruments and exposed components should be selected for the corrosive atmosphere.

The design should include:

  • Marine-compatible lifting lugs and supporting saddles
  • Removable water boxes with sufficient maintenance clearance
  • Seawater drains and high-point vents
  • Freshwater and seawater temperature instruments
  • Differential-pressure monitoring
  • Sacrificial anodes where required by the material combination
  • Isolation arrangements for cleaning without draining the complete system
  • Provisions for thermal expansion and piping loads

Electrical continuity and galvanic compatibility between titanium, stainless steel, carbon steel and connected seawater piping must also be addressed.


Lifecycle Cost Rather Than Lowest Purchase Price

The lowest-cost heat exchanger is not always the least expensive solution over the vessel lifetime. A small cooler with high pressure drop may reduce initial equipment cost but increase seawater pumping energy every hour it operates. A cheaper tube material may also require more chemical treatment, maintenance and replacement.

The preferred design should compare:

  1. Initial heat exchanger and pump cost
  2. Annual pump electricity consumption
  3. Chemical treatment consumption
  4. Cleaning frequency and labour
  5. Expected tube and gasket life
  6. Production losses caused by cooler shutdown
  7. Material replacement and disposal
  8. Environmental impact of seawater treatment and discharge

For a permanently moored platform, where the cooler may operate for thousands of hours each year, moderate investment in additional surface area and corrosion-resistant materials can produce a meaningful lifetime saving.


Recommended Preliminary Design Direction

The most sustainable starting point is a 5 MW shell and tube cooler with freshwater on the shell side and seawater on the tube side. Titanium Grade 2 tubes, titanium-compatible tube sheets, removable seawater channel covers and a low-pressure-drop flow arrangement are recommended.

For Case 1, the preliminary seawater design flow should be approximately 650–750 m³/h per cooler. For Case 2, a higher flow of approximately 850–1,000 m³/h per cooler may be needed to maintain a practical thermal approach.

The final design must optimize tube count, tube diameter, tube length, seawater velocity, number of passes, surface area and pump head as one integrated system. This approach supports the project objective of reducing energy consumption, chemical use and total operating cost throughout the offshore platform’s service life.