A steam turbine produces more useful power when its exhaust pressure is kept below atmospheric pressure. In this project, the turbine generates approximately 300 kW of electrical power, while around 3,083 kg/h of exhaust steam leaves the turbine and enters a water-cooled surface condenser. The condenser must continuously convert the exhaust steam into condensate while maintaining an operating pressure of approximately 0.5 bar absolute.
The proposed system uses a shell and tube steam condenser together with a vacuum pump and condensate-removal system. Cooling water passes through the tubes, while turbine exhaust steam enters the shell and condenses on the external tube surfaces. This arrangement prevents the cooling water from mixing with the condensate and allows the recovered water to be returned to the boiler-water system where appropriate.
At 0.5 bar absolute, the saturation temperature of steam is approximately 81.3°C. Exhaust steam entering at 100–106°C would therefore be slightly superheated. Inside the condenser, the steam is first cooled to its saturation temperature and then condensed at approximately 81°C.
Based on a cooling-water flow of 160 m³/h and a temperature rise from 66.9°C to 78°C, the heat removed by the cooling water is approximately:
Q=m˙CpΔTQ≈3600160,000×4.18×(78−66.9)Q≈2,060 kW
The estimated condenser duty is therefore about 2.0–2.1 MW. This agrees reasonably well with the heat released by condensing 3,083 kg/h of turbine exhaust steam at approximately 0.5 bar absolute.
A design allowance should be included for tube fouling, air leakage, operating variation and uncertainty in the turbine exhaust-steam condition. Final selection must be based on the actual exhaust enthalpy or steam quality supplied by the turbine manufacturer.
The low pressure inside the condenser is created primarily by the rapid condensation of steam. When steam changes into liquid water, its volume decreases dramatically, producing a low-pressure region on the turbine exhaust side.
The vacuum pump does not normally handle the complete steam flow. Its main purpose is to evacuate the condenser during startup and continuously remove air and other non-condensable gases entering through seals, flanges and piping connections. If these gases are allowed to accumulate, they form an insulating layer around the tubes, reduce heat-transfer performance and cause condenser pressure to rise.
To maintain 0.5 bar absolute at the turbine outlet, the condenser may need to operate slightly below this value to compensate for pressure loss in the turbine exhaust duct. The acceptable pressure drop must be confirmed during detailed design.
The specified cooling-water outlet temperature is 78°C, while steam condenses at approximately 81.3°C. This gives a terminal temperature difference of only about 3.3°C.
This approach is technically possible, but it requires a relatively large heat-transfer surface and clean tube conditions. The approximate logarithmic mean temperature difference is:
LMTD≈7.6∘C
Because this temperature difference is relatively low, tube fouling or a reduction in cooling-water flow can quickly increase the condenser pressure. The design should therefore include an appropriate fouling allowance, good cooling-water distribution and access for tube cleaning.
A horizontal shell and tube surface condenser is suitable for this application. Steam enters the shell through a large upper connection and flows around the tube bundle. Cooling water travels through the tubes in one or more passes. The condensate falls into a hotwell at the bottom of the shell and is removed using a condensate extraction pump or a properly designed barometric arrangement.
A removable water box gives access to the tube ends for mechanical cleaning and inspection. Depending on cooling-water quality, tubes can be manufactured from stainless steel, copper-nickel alloy or titanium. Carbon steel is commonly used for the condenser shell when the steam and condensate chemistry permits.
The condenser should also include a non-condensable-gas extraction connection, vacuum gauge, pressure transmitter, temperature instruments, condensate-level control, drain and vent connections, inspection openings and suitable supports.
Because the condenser operates below atmospheric pressure, condensate cannot always drain freely into an atmospheric tank. A condensate extraction pump is normally installed to remove the hot condensate while maintaining the condenser vacuum.
At approximately 82°C, the condensate is close to its saturation temperature at 0.5 bar absolute. This creates a risk of flashing and pump cavitation. The hotwell level, available static head and pump NPSH must therefore be carefully checked. The condensate pump should be selected specifically for hot water under vacuum conditions.
Vacuum-pump capacity cannot be determined from steam flow alone. It depends on the expected air leakage, startup evacuation time, condenser volume, cooling-water temperature and quantity of non-condensable gases in the steam.
A liquid-ring vacuum pump is commonly used for turbine condenser service because it can tolerate wet gas and small quantities of entrained steam. A steam ejector system may also be considered where motive steam is continuously available. For critical operation, two vacuum pumps can be installed in a duty-and-standby arrangement.
Final condenser sizing requires the turbine exhaust pressure and temperature, exhaust enthalpy or steam quality, allowable turbine backpressure, cooling-water quality, fouling factor, available pump pressure, permissible water-side pressure drop and preferred construction materials.
The design should also confirm whether 0.5 bar absolute is required at the turbine exhaust flange or inside the condenser. Exhaust-pipe dimensions and pressure loss are important because even a small additional backpressure can reduce turbine power output.
A water-cooled shell and tube condenser with an approximate duty of 2.0–2.1 MW is a suitable solution for condensing 3,083 kg/h of exhaust steam after the 300 kW turbine. The specified cooling-water flow of 160 m³/h, heated from 66.9°C to 78°C, is consistent with the expected condensing load.
The critical design points are the small terminal temperature difference, control of air leakage, proper vacuum-pump selection and reliable removal of hot condensate. When these factors are addressed correctly, the condenser can maintain approximately 0.5 bar absolute pressure and provide stable turbine operation.