Shell Tube Heat Exchanger for Transformer Cooling System
Time :Jul 01, 2025


Shell Tube Heat Exchanger for Transformer Cooling System


Transformer oil media characteristics

high insulation: breakdown voltage ≥ 40kV (2.5mm oil gap), need to eliminate moisture, impurity pollution;

temperature sensitivity: normal operating temperature 60-85 ℃, more than 95 ℃ to accelerate the deterioration of (acid value increase rate of> 0.1mgKOH/g・year);

gas production risk: high temperature decomposition produces H ₂, CH ₄ and other flammable gases (such as 90 ℃ gas production rate of 0.1mL/h), need to prevent gas resistance design. Gas production risk: decomposition at high temperature produces H₂, CH₄ and other flammable gases (e.g., gas production rate of 0.1mL/h at 90℃), which requires anti-gas resistance design.


Shell and tube heat exchanger technical advantages

double sealing guarantee: double tube plate structure can be used (tube plate spacing 50-100mm), to prevent cooling water leakage to the oil side (leakage rate of ≤ 10-⁶Pa・m³/s);

anti-aging design: oil corrosion-resistant materials and inert gas protection, to avoid the deterioration of the oil quality;

low-disturbance flow path: to reduce the turbulence of the oil triggered by the precipitation of air bubbles (the oil speed control of 0.3-0.3-0.5mL/h) Low-disturbance flow path: reduce bubble precipitation caused by oil turbulence (oil speed is controlled at 0.3-0.8m/s, Reynolds number Re<1500).

Shell Tube Heat Exchanger for Transformer Cooling System

Design dimensions

Thermal load calculation: Based on the transformer capacity (e.g. 100MVA transformer loss of approx. 0.5-1%, i.e. 500-1000kW), multiplied by a safety factor of 1.2-1.5.

Control of the oil-water temperature difference: Logarithmic mean temperature difference (LMTD) of ≤25°C, avoiding localized overheating on the oil side (>95°C) and preventing fouling on the water side (ΔT ≤15°C).

Pressure drop limitation: ΔP ≤ 0.5°C

- Oil side: ΔP≤0.03MPa (to prevent oil pump cavitation);

- Water side: ΔP≤0.08MPa (adapted to cooling tower head).

Insulation protection: Insulation board (epoxy resin board, thickness ≥5mm) is set between pipe and shell, withstanding voltage ≥3000V AC/1min.

Shell Tube Heat Exchanger for Transformer Cooling System