Shell and Tube Heat Exchangers for Heat Recovery in Power Generation Units
Core Selection Parameter Calculation
Heat Exchange Area Calculation: Based on the waste heat power to be recovered and the heat transfer coefficient, the formula is: Heat Exchange Area (m²) = Waste Heat Power (W) / (Heat Transfer Coefficient × LMTD).
Waste Heat Power: Taking a 1000kW diesel generator set as an example, exhaust waste heat power ≈ 1000 × 0.35 (waste heat ratio) ≈ 350kW (350 × 10³W); coolant waste heat power ≈ 1000 × 0.2 ≈ 200kW.
Heat Transfer Coefficient: Exhaust-to-water heat exchange (water in tube side, exhaust in shell side) has a coefficient of approximately 35-50 W/(m²·°C); coolant-to-water heat exchange is about 90-120 W/(m²·°C).
LMTD: LMTD for exhaust gas heat exchange is set at 80–100°C, and for coolant heat exchange at 25–35°C. If only exhaust heat recovery is required, with a heat transfer coefficient of 40 W/(m²·°C) and LMTD of 90°C, the required heat exchange area is ≈350×10³/(40×90)≈97.2 m². Allow a 20% margin during equipment selection, choosing units with ≥116.6 m² heat exchange area.
Shell-side and tube-side parameter matching:
Tube-side design: When recovering exhaust heat, the tube side carries the cooling medium (water or thermal oil). Select tube diameter 25-32 mm (seamless steel pipe), tube length 3-6 m (to avoid excessive internal resistance from excessive length), and 2-4 tube passes (to enhance medium turbulence and improve heat transfer efficiency).
Shell-side design: Shell side carries exhaust gas. Shell inner diameter is determined based on heat transfer area and tube count (e.g., for 116.6 m² heat transfer area, select shell with 800-1000 mm inner diameter). Baffle spacing is 3-5 times the tube diameter (e.g., 75-125 mm spacing for 25 mm tubes) to minimize dead zones and prevent exhaust short-circuiting.