What Are the Performance Parameters of Shell and Tube Evaporator?
Heat transfer performance parameters
Heat transfer coefficient: It is an important index to measure the heat transfer efficiency of evaporator, and the unit is W/(㎡・K). It indicates the heat transfer capacity of unit heat transfer area under unit temperature difference. Generally speaking, the heat transfer coefficient of shell and tube evaporator with ammonia as refrigerant is 582-756W/(㎡・K); and the heat transfer coefficient is 465-523W/(㎡・K) when Freon is the refrigerant.
Average heat transfer temperature difference: the average temperature difference between refrigerant and cooled medium in the evaporator, generally 4-8℃.
Heat load: the heat transferred by the evaporator in unit time, the unit is W or kW, reflecting the capacity size of the evaporator in the cooling or heating process.
Fluid Mechanical Parameters
Refrigerant flow rate: the flow rate of refrigerant in the tube, the unit is m/s. Suitable flow rate is very important to ensure the evaporation effect of refrigerant and oil return, such as dry shell and tube evaporator, the refrigerant flow rate is more than 4m/s, which is good for bringing the lubricating oil back to the compressor in the tube.
Carrier refrigerant flow rate: the flow rate of the carrier refrigerant in the shell and tube, generally 1-2.5m/s. Higher flow rate can improve the heat exchange effect, but at the same time, it will increase the flow resistance and energy consumption.
Pressure drop: including the pressure drop of refrigerant side and refrigerant carrier side, the unit is Pa or kPa. too big pressure drop will increase the energy consumption of the system and affect the operation efficiency of the system.
Refrigeration capacity parameters
Refrigeration capacity: the heat that can be absorbed by the evaporator from the cooled object or space in unit time, the unit is W, kW or RT (cold ton). It is the key index to measure the performance of the evaporator, which determines the size of the refrigeration demand that the evaporator can satisfy.
Evaporation temperature: the temperature of refrigerant evaporating in the evaporator, corresponding to the evaporation pressure, which directly affects the cooling effect and energy consumption of the refrigeration system.
Structural parameters
Heat exchange area: the total area used for heat exchange in the evaporator, unit is ㎡, generally speaking, the larger the heat exchange area is, the better the refrigeration capacity and heat exchange effect of the evaporator is.
The number of tubes and the number of shells: the number of tubes refers to the number of trips of the refrigerant flowing in the tubes, and the number of shells refers to the number of trips of the refrigerant flowing in the shells. The common number of tube strokes is 4-8 times.
Tube diameter and tube length: the inner and outer diameters of the heat exchanger tube and the length of the tube in mm, the size of the tube diameter and tube length affects the flow resistance of the refrigerant and the refrigerant carrier, the heat exchange area and the structural size of the evaporator.
Other parameters
Refrigerant charge: the amount of refrigerant to be charged in the evaporator, in kg or L. The refrigerant charge of dry shell-and-tube evaporator is less, about 35%-40% of the internal volume of the tube group; full-liquid evaporator needs to be injected with a large amount of refrigerant.
Fouling thermal resistance: reflect the evaporator operation process, heat transfer surface fouling on the degree of impediment to heat transfer, the unit is square meters・K/W. The larger the fouling thermal resistance, the worse the heat transfer effect, the system energy consumption will also increase.