A turbine lube-oil cooler loses capacity when heat transfer decreases or the required oil or cooling-water flow cannot be maintained. Common causes include:
- Cooling-water fouling: Scale, rust, sediment, biological growth, or debris inside the tubes creates an insulating layer that reduces heat transfer.
- Oil-side deposits: Sludge, varnish, and degraded-oil deposits can accumulate on the shell side, restricting flow and coating heat-transfer surfaces.
- Insufficient cooling-water flow: Blocked strainers, partially closed valves, pump wear, air locking, or low system pressure can reduce water circulation.
- High cooling-water inlet temperature: Warm cooling water reduces the temperature difference available for heat transfer, especially during summer operation.
- Reduced oil flow or oil bypassing: Incorrect valve positions, a faulty temperature-control valve, damaged baffles, or internal leakage can prevent the oil from contacting the full heat-transfer surface.
- Plugged or isolated tubes: Fouled tubes or tubes that have been plugged after leakage reduce the effective heat-transfer area.
- Air or gas accumulation: Trapped air creates poorly cooled areas and interferes with fluid circulation.
- Tube corrosion or erosion: Wall thinning, surface damage, or deposits from corrosion can reduce thermal performance and eventually cause leakage.
- Incorrect operating conditions: Higher turbine load, increased oil temperature, changed oil viscosity, or flow rates above the original design may exceed the cooler’s rated capacity.
- Poor maintenance or incorrect reassembly: Damaged gaskets, missing seals, incorrectly installed baffles, or internal bypassing after maintenance can significantly reduce performance.
A gradual increase in oil outlet temperature or pressure drop usually indicates fouling. A sudden loss of capacity is more likely related to a failed pump, blocked strainer, incorrect valve position, control-valve malfunction, or internal bypassing. Performance should be evaluated by checking oil and water inlet/outlet temperatures, flow rates, pressure drops, valve positions, and surface cleanliness.