An air-compressor heat-recovery unit can typically produce hot water at approximately 45–70°C, depending on the compressor type, oil or coolant temperature, water flow rate and heat-exchanger design. Oil-injected screw compressors often discharge oil at around 70–95°C, making a stable hot-water outlet temperature of 50–65°C practical for many installations.
Higher temperatures approaching 70–80°C may be possible when the compressor operates continuously at a high load and the available oil or coolant temperature is sufficiently high. However, the hot-water outlet temperature must remain below the heat-source temperature with an adequate approach temperature for reliable heat transfer. Reducing the water flow can increase outlet temperature, but it also reduces the total recovered heat and may create unstable control conditions.
The achievable temperature also varies with compressor load. During part-load operation, less waste heat is available, so the outlet-water temperature may fall unless the system includes a storage tank or auxiliary heater. For applications requiring a constant temperature, the recovery system can use a buffer tank, circulation pump, temperature-control valve and backup heating source.
When selecting the heat-recovery unit, the compressor oil or coolant flow, inlet and allowable outlet temperatures, water inlet temperature, required water flow and target outlet temperature should all be provided. The exchanger must be sized not only for the desired water temperature but also to maintain the compressor’s required operating temperature and acceptable pressure drop.